ftse-ge51
ftse-ge51colres.jpgDownloads
ftse-ge51bwhres.tifDownloads
Frost protection thermostats are installed on the air side for the purpose of protecting air conditioning units, heat exchangers, radiators, and similar installations against damages due to frost or freezing.
Control input signal 0..10V=
Temp. setpoint range 1 ... 10 oC
Output Signal 0..10V: Input/Temp.
Ambient temperature 15 ... 15 oC
Switch function/capacity SPDT 250 Vac Microswitch / 8A
Reset function reset inside
Thermostat application frost protection thermostat, 2-phases
Mounting place air duct
IP class IP40
Power supply 24 Vac | 7 VA 
Temperature element capillary
Setpoint device inside
Additional description The 0-10V output signal is the maximum of the input signal and the temperature value (10-0 degrees C = 0-10V)
Capillary tube lengthTypeDownloads
m TXTPDF
2FTSE20 TXT
PDF
Specification sheet (English) Specification sheet (German) Installation/mounting instruction (German) Installation/mounting instruction (English) Installation/mounting instruction (French) Installation/mounting instruction (Spanish) Certificate (English)
6FTSE60 TXT
PDF
Specification sheet (English) Specification sheet (German) Installation/mounting instruction (German) Installation/mounting instruction (English) Installation/mounting instruction (French) Installation/mounting instruction (Spanish) Certificate (English)