Control software |
control software embedded, with hundreds of different selectable applications and parameter settings |
Hardware inputs |
• |
Analog Inputs (AI) for NTC20k sensors, 0..10 V, 0/4..20 mA active sensors (apply signal separator!) or slow switching dry contact |
• |
Digital Inputs (DI) for potential free contacts, 24 Vdc or 24 Vac |
|
Hardware outputs |
• |
Analogue Outputs (AO) 0..10V= |
• |
Digital Outputs (DO) relay contact SPDT or SPST |
|
Management applications |
ARENA / RANGER |
Stand-alone operation |
yes |
Bus system description |
LonWorks(R) bus for data exchange with other TIGER, or PANTHER controllers, and building automation management systems with ARENA, or alarm monitoring with RANGER |
Transceiver type |
LonWorks(R) FTT10A |
Mounting |
DIN rail |
Protection class |
IP30 |
Type of terminals |
screw terminals with terminal block |
Memory back-up |
goldcap capacitor for 72 hours buffer |
Power supply |
24 Vac | 15 VA |
LonWorks(R) connection |
directly connectable |