Heating systems: Freely programmable IP networked, large size application (Excel Web)

xl1000age51
This solution example provides control of a multi boiler sequence, including
• 2-stage burner control with alarm input
• boiler return water control (incl. return water temperature minimum limitation)
• sensors for boiler temperature and boiler return water temperature
• boiler safety thermostat
• boiler pump control and alarm
• sensor for common supply water temperature
• boiler strategy incl. boiler sequence cycling
• general emergency-off input
In addition the following integrations are possible:
• Embedded IP connectivity (e.g. Ethernet LAN/WAN)
• Embedded BACnet protocol (BTL listed)
• Embedded web-capability; Excel Web can be operated directly by Internet Explorer or Mozilla Firefox.
• Embedded LON protocol - Excel Web supports up to 300 or 600 NVs.
Physical I/O's can be Honeywell Smart I/O's, Smart I/O Compact, Distributed I/O's or 3rd party LON I/O's.
Honeywell Smart I/O's offer the unique benefit of
• 230 Vac or 24Vac versions
• various point mixes
• fixed or removable terminals
Application diagram and Product list
applimage-7age51
Product descriptionType
Excel Web ControllerXL1000C500
(1) Safety thermostatSTB1
(2) ValveV5011R1083
(3) ActuatorML7420A6009
(4) Boiler temperature sensorKTF20
(5) Supply water temperature sensorVF20T
(6) Return water temperature sensorVF20T